1794 FLEX I/O FLEX I/O Modules FLEX I/O offers all the functions of larger rack-based I/O without the space requirements. Its cost effectiveness, flexibility, modularity, and reliability have made it the most popular distributed I/O platform with over 4 million modules sold. For additional information on FLEX I/O systems and modules, refer to the following documents: Catalog Publications Number Voltage Description Installation Instructions User Manual 1794 1794 FLEX I/O Product Data 17942.1 1794ACN 24V dc ControlNet Adapter 17945.8 1794ADN 24V dc DeviceNet Adapter 1796.5.5. Apr 19, 2018 How I set up and test the AB Ethernet 10/100 communication module. Using RSLinx and BootP server Ver 2.3 To reset the Series B modules to factory default - power off. Set the switches to 888.
Advertising
Chapter
4
Publication 1794ĆUM009D-EN-P - April 2004
Troubleshooting
In this chapter, we tell you:
•
about the indicators on the module front plate
•
how to use the indicators for troubleshooting the module
Three conditions can cause the remote I/O adapter to declare a
communication fault.
•
no remote I/O (link) communication for more than 100ms
•
no commands issued to this address over the remote I/O link
within the last 255 link transactions https://bloomnew221.weebly.com/blog/lg-g3-user-manual-pdf-download.
•
communication is lost to a module when Rack Fault Select is
enabled ![]()
When any of these conditions exist, the adapter will:
•
reset all digital outputs or leave them in their last state (depending
on the position of the last state switch, S2-1). Refer to page 2–9 for an explanation of analog module responses.
A communication fault will be automatically cleared by a command
from the processor if PRL (processor restart lockout) is not selected, or by pressing the reset switch on the front of the module if PRL is selected. https://bloomnew221.weebly.com/blog/keurig-k-mini-plus-user-manual.
Adapter Fault
Local Fault
Adapter Active
ACTIVE
PWR
AllenĆBradley Danfoss vlt installation manual.
FAULT
LOCAL Morefit slim fitness tracker user manual free download.
FAULT
ADAPTER
Power ON/OFF
Reset Switch
Important: Cycling power to the adapter will also reset faults.
However, any queued block transfers will be lost, and
all outputs will turn off, regardless of the position of the last state switch.
The module has indicators on the front plate as shown below. Use
these indicators for troubleshooting the module. The following tables describes problems that may occur, probable causes, and recommended courses of action.
Chapter Objectives
Fault Conditions
Troubleshooting with the
Indicator Lights